Xiamen Xingruijia Import and Export Co., Ltd. has been specializing in the sales of industrial control equipment spare parts for 20 years. For more ABB models, please refer to the product list . If you need other brands or models, please contact us. We have a variety of brands and models in stock, and we can purchase difficult to order models for you. We look forward to your inquiry!!!
First hand source//affordable price//Spot inventory!
•Shipping Port: Xiamen
•Manager: Rhonda
•E-mail: sales7@saulplc.com
•Tel/WhatsApp/Wechat: + 86-15359273796
•Ship to you via Fedex/DHL/TNT/UPS/EMS
•Package: Original packing with cartons
ABB HC-C-AM801F-X-10
The ABB HC-C-AM801F-X-10 is associated with the ABB AM801F battery backup module used in the ABB AC 800F controller platform, part of the Freelance and Advant OCS automation systems.
The AM801F is designed to provide battery-backed retention of CPU memory data when the AC 800F controller is switched off or temporarily loses its normal power supply. It helps preserve configuration data and real-time clock settings during maintenance and power interruptions.
The standard AM801F is identified by ABB part number 3BDH000040R0001. The HC-C-AM801F-X-10 designation appears in industrial spare-parts listings as an AM801F-related product reference.
Core Functions
-
Memory Backup: Provides battery buffering for AC 800F controller memory.
-
Configuration Retention: Helps preserve controller configuration data when the controller is powered down.
-
Clock Backup: Maintains real-time clock information during power interruptions.
-
Battery Monitoring: Monitors battery condition and provides low-battery status indication.
-
Electrical Isolation: Supports electrical isolation of bus signals, allowing module insertion and removal under specified operating conditions.
-
System Reliability: Reduces the risk of configuration data loss during controller maintenance and module replacement.
Technical Parameters
|
Parameter |
Specification |
|
Manufacturer |
ABB |
|
Model |
HC-C-AM801F-X-10 |
|
Associated Module |
AM801F |
|
Standard ABB Part Number |
3BDH000040R0001 |
|
Product Type |
Battery Backup Module |
|
Product Family |
ABB AC 800F |
|
Automation Platform |
Freelance / Advant OCS |
|
Backup Battery |
3.6 V Lithium Battery |
|
Battery Type |
SB 808F |
|
Battery Holder |
SY 809F |
|
Battery Monitoring |
Batt Low Indicator |
|
Status Indicators |
State LED and Batt Low LED |
|
Installation |
AC 800F controller housing |
|
Main Function |
CPU Memory Backup |
Product Features
-
Reliable Memory Protection: Provides backup power for retaining important controller memory information.
-
Lithium Battery Technology: Uses a 3.6 V lithium battery for memory buffering.
-
Battery Condition Monitoring: Includes a dedicated Batt Low indicator to identify insufficient battery voltage.
-
Hot-Swap Support: Its electrical isolation design supports insertion and removal under specified AC 800F operating conditions.
-
Compact Modular Design: Fits into the dedicated module slot of the AC 800F controller.
-
Configuration Security: Helps protect stored configuration information during maintenance and power interruptions.
Hardware Composition
The ABB AM801F module mainly consists of the following components:
-
Battery Holder: Accommodates the replaceable lithium backup battery.
-
Lithium Battery: Provides energy for CPU memory buffering.
-
EEPROM: Stores module configuration information.
-
Electrical Isolation Circuit: Provides isolation of bus signals.
-
Battery Monitoring Circuit: Monitors battery voltage and generates low-battery indications.
-
State LED: Indicates module operating conditions.
-
Batt Low LED: Indicates missing or insufficient battery voltage.
Typical Applications
-
ABB AC 800F controller systems.
-
ABB Freelance distributed control systems.
-
ABB Advant OCS automation platforms.
-
Industrial process control systems.
-
Power generation automation.
-
Chemical and petrochemical plants.
-
Manufacturing production lines.
-
Industrial controller memory backup applications.
Maintenance Considerations
-
Regularly check the Batt Low LED to monitor battery condition.
-
Replace the battery when its voltage becomes insufficient.
-
Use the specified 3.6 V lithium SB 808F battery.
-
Follow the recommended battery replacement procedure.
-
Avoid removing the battery holder when no alternative backup battery is available, as controller memory data and real-time clock settings may be lost.
-
Check module contacts and connectors for oxidation or contamination.
-
Observe electrostatic discharge precautions during installation.
-
Confirm compatibility with the CPU board, particularly when using PM802F or PM803F configurations.
Important: ABB documentation specifies that AM801F does not provide battery buffering when used with the PM803F CPU board.
Overall Evaluation
The ABB HC-C-AM801F-X-10 AM801F Battery Backup Module is an important auxiliary component for ABB AC 800F controller systems. Its primary purpose is to protect controller memory and configuration information through battery-backed operation.